ETI0003-FA1/20/120 Standard Front Panel Layout (w/ Remote Control Panel off)

ETI0003-FA1/20/120 Standard Rear Panel Layout
The field proven Rugged Systems™ Power Distribution Unit (PDU) line is ideally suited for military, industrial and telecommunications applications requiring a rugged rack, vehicular or field deployable, high reliability, compact size and light weight design. The heavy-duty chassis occupies only 2U (3.5”) of rack space while controlling up to 2400 VA of power via six double pole controls. The rounded metal corners and rugged handles aid in safe handling. Internally, all major components are well secured and electrically insulated to prevent damage due to shock and vibration. All controls and protective devices are brought to the front panel with critical switches or breakers guarded. Further, all front panel devices are recessed to prevent damage or accidental operation. The control panel contains individual control breakers, alarm silence switch and alarm LEDs.
The LED arrays keep the operator informed as to the unit's status. An alarm will flash its respective LED until acknowledged. Once the alarm reset is pressed, the LED will remain on steady until the alarm is cleared. The intelligent PDU allows control of the individual output circuits incorporating thermal and interlock interfaces for additional control and safety, plus Battleshort override. Each load can have an external interlock to turn off power to equipment when it is not fully engaged in the rack or becomes overheated. The rack may be equipped with both a thermal warning and a thermal shutdown sensor that the PDU uses to alarm and shut down all the loads to avoid damage or thermal runaway. A Battleshort signal will override both the thermal and interlock signals. An external Fan Fail or auxiliary alarm signal can also brought in to annunciate. The high intensity audible alarm can be heard in high noise environments, yet is easily adjustable to suit quieter conditions. The double pole input breaker provides overload and short circuit protection for the connected UPS input isolation transformer and rack fans. The PDU circuit breaker on/off operation is also interlocked to control the UPS on/off function as well. Power from the UPS is brought back to the PDU to be distributed to the loads. Each load is controlled by a double pole solidstate relay avoiding accidental operation due to shock or vibration. The elapsed time hour meter tracks the rack equipment operation for maintenance.
The rear panel provides locking connectors for the input power, output power, alarm and control signals. Appropriate jumper plugs are available for options not used in a particular rack system.
Overall, the PowerStation product line is uniquely qualified for critical shipboard, vehicle, airborne or land based systems combining advanced modular design features with highly reliable construction.
Technical Specifications
| AC INPUT FROM RACK | |
| PDU input from rack: | 120 VAC nominal, optional up to 600 VAC |
| INPUT MAIN (J11) connection: | MS3474W18-8P, 8 pins, locking |
| Input protection: | Guarded 2 pole, 20 amp circuit breaker |
| Input control: | Guarded 3 pole, 20 amp toggle switch |
| Input power indicator: | Green neon lamp |
| AC OUTPUT TO UPS | |
| PDU output to UPS: | Same as input from rack |
| AC TO UPS (J11) connection: | Uses same connector as input from rack |
| AC INPUT FROM UPS | |
| PDU input from UPS: | 120 VAC, 60 Hz nominal, standard UPS |
| AC FROM UPS (J10) connection: | MS3474W14-4P, 4 pins, locking |
| AC OUTPUT TO FANS | |
| PDU output to fans: | Same as input from rack |
| AC TO FANS (J12) connection: | MS3474W16-8S, 8 sockets, locking |
| POWER DISTRIBUTION | |
| PDU output voltage to loads: | 120 VAC, 60 Hz nominal, standard UPS |
| Output rating to loads: | Limited to lesser of 20 amps or UPS rating |
| Output circuits: | Six controlled outputs w/2 pole ss relays |
| Output protection: | Guarded individual 2 pole circuit breakers |
| CNTRLD AC OUT 1-5 (J13) connection: | MS3474W20-16S, 16 sockets, locking |
| CONTROLLED AC OUT 6 (J3) connection: | MS3474W14-5S, 5 sockets, locking |
| THERMAL CONTROL | |
| Control function: | Two stage thermal warning and shutdown |
| THERMAL CONTROL (J6): | AMP 206705-1, 9 pins, locking |
| INTERLOCK CONTROL | |
| Control function: | Microswitches sense each equipment position Disconnects power to load when racked out |
| INTERLOCK (J8) connection: | AMP 206036-1, 16 pins, locking |
| REMOTE CONTROL | |
| Output control/alarm silence: | Local/remote control panel w/rocker switches |
| Operational status: | LEDs for LOW BATT, AC FAIL, WARM, HOT, CPU Adjustable +90 dB audible alarm |
| REMOTE CONTROL (J9) connection: | MS3474W14-18S, 18 sockets, locking |
| UPS INTERFACE | |
| Control function: | AC Fail & Low Battery signals, UPS on/off control |
| UPS (J7) connection: | AMP 206043-1, 14 sockets, locking |
| MECHANICAL | |
| Dimensions ( H x D x W ): | 3.5 (2U) x 15.0 x 19.0 in (89x381x483mm) |
| Rack Slide Mount Patterns: | Slides or rear support mounting brackets |
| Alternate Mounting Options: | Table, Wall, Floor, Portable, Horizontal/Vertical |
| Shipping weight: | 20 lb. (9.1 kg) with lift handles front |
| Audible noise: | Less than 47 dB @ 5.0 ft., ANSI "A" scale |
| Cooling type: | Convection cooling |
| ENVIRONMENTAL | |
| Storage temperature: | -13° to 140° F ambient (-25° to 60° C ) |
| Operating temperature: | 32° to 122° F ambient (0° to 50° C ),higher optional |
| Operating humidity: | 0 to 95% relative humidity (non-condensing) |
| Operating elevation: | Up to 15,000 ft (4,572 m), higher optionally |
| STANDARDS | |
| United States: | Meets UL-1778 standard, MIL STDs 901, 167 & 1399 Shock/Vib/Electrical |
| Canada: | CSA C22.2 No. 107 safety requirements |
| EMI Protection: | EMI/RFI FCC, Class B, MIL STD 461 |
| OPTIONAL ACCESSORIES | |
| Dual Source Input, Emergency Power Off, EMI Insertion Loss Filters, Auxiliary DC Power Supply, MS Connectors, Transient Surge Suppression, Load Sequencing | |